Which contactor to choose for an electric water heater
Please tell me which contactor to use for a heater with a maximum power consumption of 6 kW, 220 / 380V, each heater for 2 kW, for what power and for what current?
Please tell me which contactor to use for a heater with a maximum power consumption of 6 kW, 220 / 380V, each heater for 2 kW, for what power and for what current?
We recommend reading:
How to conduct electrical wiring in an apartment - all stages of electrical installation
If we are talking about a three-phase network, the load is 2 kW on each phase, then choose a contactor whose power contacts are designed for a current of at least 10 A. At a load of 2 kW, there will be a current of almost 10 A. on each phase.