What cable section is needed for a 3 kW hob?

Edward asks:
Hello, I plan to take a hob with two burners with a total power of 3 kW, a 3x4 mm cable and an automatic machine for 20A will be enough?

The answer to the question:
Hello! It will be enough from the point of view of the current load, but there is such clause 10.2 in SP 256.1325800.2016, which states that single-phase electric stoves should be connected with a cable with copper conductors with a cross section of at least 6 mm².