In the floor guard, plug 20A, which machine to put?

Good afternoon help me if I made the following scheme correctly:

Floor plate 380 20A - circuit breaker - counter Meredian SOE-1.02 / 2 - AB S-16A (general, 2 poles), AB V-10A (light), AB V-16A (hall, 2 modules, 4 sockets in one module, on one module 2 cables 2.5), AB V-16A (bedroom, hallway, 1x2 sockets in one module, on one module 2 cables 2.5, 1x4 sockets in one module, on one module 2 cables 2.5), AB V-16A (kitchen , 2 modules, 4 sockets in one module, 2 cables 2.5 for one module), AB V-16A (kitchen, 1x2 sockets, 1 cable 2.5 for one module (without a break, from the machine to the socket).

Questions:

  1. Will the automatic machines work correctly and won't plug the cork in the floor guard according to this scheme?
  2. I tried to take the load, but I didn’t calculate something correctly if the computer works at about 600W, a 15L 1500W boiler, refrigerator, TV, washing machine, light in several rooms 70W (diode lamps), a 1500W vacuum cleaner, the machine doesn’t work according to my scheme disconnect? Is there enough load?
Loading...

One comment

  • Admin

    In total, your load is less than 4 kW, and an automatic machine with 20 Amps will provide 4.5 kW, that is, it can withstand.