Check the circuit diagram of a country house
1. C6 - 1.5 mm (Imax = 16A) - 16A socket - refrigerator (power up to 1 kW, current up to 4.5A)
2. C6 - 1.5 mm (Imax = 16A) - light on both floors and porch (a total of 1.0 kW, current 4.5A)
3. B32 - 6.0 mm (Imax = 40A) - heating (convectors connected without sockets) ground floor and terrace (total 6 kW, current 27.3A)
4. V25 - 2.5 mm (Imax = 25A) - stove, kettle, water heater, socket 16A (total 5.0 kW, current 22.7A)
5. C16 - 2.5 mm (Imax = 25A) - sockets 16 A first, second floors, terrace (total 3.0 kW, current 13.6 A)
6. C25 - 2.5 mm (Imax = 25A) - a street shower (2 kW) and a street socket for a mower, inverter and other tools (total 4.5 kW, current 20.5A)
The questions are as follows:
1. Are there any significant errors in the circuit?
2. Is it possible to lay two or more cables in one corrugation?
3. I want to use the NYM brand, is this the right decision?
It is allowed to lay cables in blind ducts with 35% filling of their total area (PUE p. 2.1.61), this rule can be extended to corrugation. That is, just pick up a larger corrugation. But are you sure you want to save so much? Your line is not along a kilometer ...
Good afternoon.
Country house. According to TU 8.5kW 220V. It is required to establish PZR and OP.
What set of equipment (preferably Schneider) is needed and in what sequence (from input) should it be installed?
Now: A25 Schneider submachine gun, counter, RCD Schneider.