Cable cross section for connecting a 5 kW water heater and sockets

Nikolai asks:
1.5mm cross-section wiring cable, 5000 kW instantaneous water heater 2.5mm cross-section wire with 25A diffavomat. Is it possible to distribute the load of a wire with a cross-section of 2.5 mm into two outlets with a cross-section of a wire of 1.5 mm each and have separate breakers?
The answer to the question:
You do not quite clearly formulate the question. No. Lay the sockets with a CABLE (not a wire!) With a core section of 2.5 mm². What does it mean to split the wire, but at the same time someone has separate automatic shutdowns? On sockets automatic no more than 16A. On a flowing water heater "5000 kW", and correctly it will be 5000 watts (5 thousand kilowatts - this is already some kind of power plant), install a separate machine. And the cable on it is better than 4-6 mm², since 2.5 is not enough.
If I misunderstood and you want to connect the water heater through two plugs to two sockets - they don’t do that, such devices are usually connected directly to the cable.