Good evening. Please tell me, can I use a 32A single-pole circuit breaker to connect the hob? Or do you need a 32A difavtomat?
Good evening. Please tell me, can I use a 32A single-pole circuit breaker to connect the hob? Or do you need a 32A difavtomat?
We recommend reading:
How to conduct electrical wiring in an apartment - all stages of electrical installation
Hello! For the hob, you need to use a single-pole circuit breaker - to protect against overload and short circuit currents, and necessarily another protective device - a residual current device - to protect against electric shock and fire due to current leaks. Difavtomat is a combined protective device that performs the functions of an automaton and an RCD. That is, choose one of the options - either a difavtomat or an automatic machine + RCD.
And without ouzo and difavtomat you can connect?
It is possible, but it is not safe.