Can I connect a hob, stove and dishwasher to a 40A outlet?

Is it possible to connect a 3.3 kW hob, 4.6 kW hob and a 2.8 kW dishwasher to a 40 A power outlet, provided that the dishwasher consumes 0.8 kW per cycle?

Loading...

One comment

  • Admin

    Hello! It is possible, but provided that you do not turn on all this at the same time, so that the current does not exceed the rated current of the outlets. In addition, the wire to the outlet should come no thinner than 4 square meters. mm if the gasket is open, and if closed from 6 square meters. mm for single-phase network.
    But I would do otherwise.
    If the network is still single-phase: install an electrical panel on 6 modules, plastic, so as not to spoil the interior. In the place of the outlet, lead your cable into the shield and connect each of the devices to its difavtomat.