What introductory machine to put if allocated 15 kW 380 volts?
Good afternoon. I bring to the house 380v, the shield has collected the introductory. Automatic 3p 25a (Schneider brownie), automatic 16a (Schneider brownie) and socket on din rail. This is a street shield. A house shield is installed on 36 modules. In this shield, too, set the 3p switch to 25a? Or below par? Or put it in the opening shield at 32a for example, and in the house at 25a? Allocated 15 kW 3ph. And another question is: which company to choose group switches for 10A and 16A? Schneider, ABB or Legrand. I would like to collect the shield with the legend.
Hello! 25 amperes is your maximum, it makes no sense to put higher. In your case, on sockets 16 Amps, on lighting 6-10 Amps. Manufacturer company, choose any of the above, all of high quality. But I would choose ABB.
Thanks for the answer. On the street at 25A and the house? The same money? And how many pole set 3 or 4?
Zero should disconnect the same?