How to calculate the cable cross section 80 m long for connecting a load of 3 kW?
How to calculate the cable cross-section if the power consumption is 3 kW, and the cable length from the shield to the consumer is about 80 meters. And is the machine suitable for 25A?
p.s. Excessive denomination does not mean that it does not fit. Just this is more than enough and it will pull up to 5 kW with a single-phase connection. It all depends on the other end of the line - if there are sockets, then put the machine on 16A.