How to lay a 36V line and connect the wires in it?

Farit asks:
The voltage from the secondary winding of the toroidal transformer 36 V must be laid on the street, in a metal profile 40 * 30 consisting of two halves and PUGV wires connected by bolts connected by a VAGO connector
Do you need to remove the connection in the corrugation of 20 mm and close the connection with the coupling sleeve? Thank.
The answer to the question:
Hello, the use of corrugation in this case is not necessary (the cable will already be in the tray, so to speak). It’s better to make connections anyway, or weld. WAGO is not the best choice, what current will be in the circuit? What is the power of the transformer? Using a coupler is good, but not necessary (but desirable)