How to connect a heating element of 9 kW - the choice of cable cross-section and the rating of the machine
Hello! I have a 9 kW electric heater installed in the boiler, I want to connect it as 6 kW (I don’t know how many amperes). Which cable to put and the machine for how much A?
What cable (cross-section) and the rating of the machine I also can not tell, because you did not say 220 or 380V with you. If 220, then for a 9 kW boiler, a 50A automatic machine is needed, the cable is not less than 6, and preferably 10 mm². If 380, then an automatic machine on 16A and a cable with a cross-section of 2.5 mm².