How to find out the utilization of horizontal and vertical earthing switches?
How to find out the utilization factor of horizontal and vertical earthing switches knowing the number of vertical electrodes - 3 pcs. their length is 4 m. and the distance between them (length of the connecting strip) is 4 m. What to divide and multiply. Relationship tables do not help. There are no such characteristics. Thanks in advance.
The ratio of the distance between the electrodes to their length(a/lat) |
Number of electrodes |
ηat |
1 |
2 3 5 10 15 20 |
0,84-0,87 0,76-0,80 0,67-0,72 0,56-0,62 0,51-0,56 0,47-0,50 |
2 |
2 3 5 10 15 20 |
0,50-0,92 0,85-0,88 0,79-0,83 0,72-0,77 0,66-0,73 0,65-0,70 |
3 |
2 3 5 10 15 20 |
0,93-0,95 0,90-0,92 0,85-0,88 0,79-0,83 0,76-0,80 0,74-0,79 |