How to find out the utilization of horizontal and vertical earthing switches?

Michael asks:
How to find out the utilization factor of horizontal and vertical earthing switches knowing the number of vertical electrodes - 3 pcs. their length is 4 m. and the distance between them (length of the connecting strip) is 4 m. What to divide and multiply. Relationship tables do not help. There are no such characteristics. Thanks in advance.
The answer to the question:
How is it not such characteristics? You have 3 electrodes of 4 meters each, you determine how far they are from each other. Once the strip is 4 meters, suppose that these electrodes will be 1.3 meters apart (at least in a row, at least with a triangle), then the ratio of distance to length is 4 / 1.3 = 3.07. We round down (up to three), we have 3 electrodes, from the first table found in Google - the utilization coefficient is 0.90-0.92.

The ratio of the distance between the electrodes to their length(a/lat)

Number of electrodes

ηat

1

2

3

5

10

15

20

0,84-0,87

0,76-0,80

0,67-0,72

0,56-0,62

0,51-0,56

0,47-0,50

2

2

3

5

10

15

20

0,50-0,92

0,85-0,88

0,79-0,83

0,72-0,77

0,66-0,73

0,65-0,70

3

2

3

5

10

15

20

0,93-0,95

0,90-0,92

0,85-0,88

0,79-0,83

0,76-0,80

0,74-0,79

 