Is cable allowed to pass through a partition in a PVC pipe?
In accordance with the requirements of clause 2.1.58 of the PUE and clause 3.18 of SNIP 3.05.06-85, cable passages through partitions are performed in pipe sections or in ducts. Is it permissible for 220 V cables to pass through a fireproof partition to protect not with a metal pipe, but with a PVC pipe?
Hello! It is possible, you can use the PND corrugation yet. You can sewer, the purpose of the pipe is to protect the cable from damage as a result of settling of the wall or grinding.
I will repeat your SNIP item:
Building Norms and Rules SNiP 3.05.06-85 "Electrical Devices"
paragraph 3.18.
“The passages of unarmoured cables, sheathed and unprotected wires through fireproof walls (partitions) and interfloor ceilings must be made in pipe sections, or in ducts, or openings, and through combustible - in segments steel pipes. "
Those. not regulated material for fireproof walls.