Help solve the problem with the generator
Good hour to all. Help to understand the problem. I'm not special, but I understand something. There is a country house. There is a shield. There are three Resant 8000 stabilizers. I decided to make a reserve, set the ABB circuit-breaker and energized one phase in case of a power outage. In general, a few days ago I rented a five kW generator. I connected and started - the usual LEDs blinked. In general, the consequences - the stabilizer does not work, the screen shows the input and output voltage, but there is no output 220. I had to switch to bypass. And how to make zero on the generator? Thank you all in advance.
One of the wires from the generator must be connected to the ground loop. It automatically becomes zero. The stabilizer must be carried in for repair.