    Connecting a heated floor through a socket is basically acceptable if the socket is designed for 16A, and the power of the connected warm floor does not exceed 3.5 kW. Also, grounding in the outlet and the same terminal in the plug must be provided. But it is better to stretch a separate cable from the shield.