Evaluate the assembly scheme of the shield in a one-room apartment
Good afternoon. Recently received the keys to a one-room apartment, the question became electricians. On the landing:
- Introductory machine IEK C50
- Mercury 200 Counter
- Selective RCD IEK 63A 100mA
- An VVG NG LS 3x10 cable enters the apartment, there is no wiring in the apartment.
Will be used:
- Cable for sockets VVGp NG LS 3х2.5 mm
- Cable for NYM hob 3X6 mm
- Cable for lighting VVGp NG LS 3x1.5 mm
There will be no junction boxes; the wiring will be done in the socket boxes. I would like optimality and stability in the circuit. Please give constructive criticism.
The scheme is acceptable, it is only better to separate the group of lights and sockets, do not install on one RCD.
Those. hang on one RCD all the equipment, including and on the hob and oven, and set the released RCD to the light, is that right?
No. shine. Or connect through an additional RCD, or if it is not possible, then a separate line through the machine. Why do this - to exclude the possibility of being left without light when the machine switches off in case of an accident in consumers of the outlet group.
Those. Is the circuit above incorrect?
Those. it needs to be improved a bit.
????
Poke your nose please, I just can not find the error.