Do I need to lay a separate cable for the induction panel in a new building?

Hello! A new house, a new building, the house was commissioned with new electric stoves (capacity 7 thousand watts). Subsequently, an induction panel (4,600 W) and an oven (independent, 3,500 W) were purchased. When connecting, some incoming experts advise throwing a separate cable for induction, and someone says that there is no need, the wiring will withstand. Which solution will be right? Thank!

Loading...

One comment

  • Admin

    Hello! If the walls are laid wires 4 square meters. mm and thicker - do not worry. Moreover, the house is designed for electric stoves, provided that you have an electric project calculated according to the norms. With the same success, you can advise a separate cable for the oven, and even for all burners and the oven to work at the same time - this is extremely rare. Check the cross-section of the wire conductors to which the furnace is connected in general - and use it for health.
    P.S.
    You can install a small shield near the stove and cabinet with two AB and UZO on the stove and cabinet, respectively.

    To answer

Add a comment