Is it possible to reduce the power of the EVAN electric boiler?

Hello! Please advise whether it is possible to reduce the power of the EVAN C1 9 220V boiler by simply removing the terminal from one TEN or from two? The boiler does not provide for their separate shutdown. The boiler was too powerful for a heated room. Is it necessary to disconnect both phase and zero, or is it only enough phase? Does the starter need to be changed, or does it not affect such changes? Thank you so much in advance.

Loading...

One comment

  • Admin

    Hello! Yes, just turn off the heating elements, you can not touch the zeros, you can turn them off. Just discard and insulate the phase conductor from unnecessary heating elements. Do not touch the starter (contactor).