Is it possible to put a machine with a higher face value if it knocks out electricity?
Hello, tell me please, the power consumption does not draw out for me. That is, I turn on two heaters and everything, immediately knocks out electricity. Is there a 16 A fuse? If I set the same in front of it, but at 25A, will it also knock out?
Hello! It still will not save, because the circuit will remain protected by overload machine 16A. In addition, such manipulations as replacing a machine with a higher nominal value entail very dangerous consequences: due to overload, the wiring may not withstand, melt and a fire will occur in the house. You can change the machine to a higher nominal value if the wiring is able to withstand the load in the apartment or house. To put a 25A automatic machine, the wires must be a cross-section of at least 2.5 mm.kv. (copper). In your case, you can either use one heater, or change the wiring and input cable to new, larger cross-section.