Which magnetic starter to choose for a 6 kW boiler?

I dream of turning on and off remotely an electric boiler of 6 kW, an automatic machine for 32A using a GSM relay (SimPal - D210) with a maximum load of 8 A, 1700 W, 110-230 V. Which magnetic starter (contactor) needs to be selected to turn the boiler on and off with appropriate parameters? Thank you for the attention!

(1 votes)
Loading...

2 comments

  • Admin

    A power of 6 kW is a current of just over 27 A. Choose the closest higher rating of the contactor (magnetic starter) of the manufacturer you choose - usually 32 A. The control coil of the contactor (starter) should be designed for a household voltage of 220-230 V.

    To answer
  • Elena

    32 and more

    To answer