Which cable to choose for connecting an oven with a capacity of 3.1 kW?

Oven with a capacity of 3.1 kW. Which cable lead to the shield from the outlet? Interested in the choice of cable cross-section.

(1 votes)
Loading...

5 comments

  • Admin

    2.5 mm square copper cable can withstand up to 4.5 kW without problems, in your case it will even be with a margin. As for the cable brand, specify more about where the cable will be held (wall material and other important features). Also note that the outlet must be rated for 16A.

    To answer
  • Alexei

    walls concrete panel strobes further in the boxes

    To answer