Which RCD to choose for the pumping station?

Yuri asks:
Hello. There is a pump station jilex jumbo, power consumption of which is 1100 watts. The wire to this station stretches 3x2.5 square meters. mm., automatic respectively 16a. The instructions indicate that it is forbidden to use the station without an RCD. Is an RCD suitable for this unit at 25A 30mA? How to choose the type of leakage current A or AC?
The answer to the question:
Hello! Yes, an RCD for 16-25A with a current of no more than 30mA is suitable. As for the type, at least A, at least AC, a sinusoidal leakage current is possible here, the pulse in an induction motor, as I think, can not come from.