What to put difavtomaty for sockets in the kitchen?

Vyacheslav asks:
In the kitchen they made a new wiring num 2.5. Divided into two lines: the first will be connected washing machine, microwave, thermo pot or kettle, small household appliances if necessary. The second line: air conditioning, kettle or thermal sweat, small household appliances as needed. Both lines are displayed in an electric shield, it is necessary to power all this.

The question is, do you need two 20A difavtomats for each line, or can you combine two lines and feed everything to one 40A difavtomat? What kind of difavtomats are needed (there are a lot of any ac-abbreviations, some pi, etc., etc.), what parameters should I look for when choosing a difavtomat?

The answer to the question:
Hello! Let's think from the other side. Why did you make two lines? To put them on one machine? On sockets put machines no more than 16A. Because any modern outlet is designed for 16A, less often for 10A. Therefore, 20 and even more so 40 amperes should not be set. Large ratings are placed on individual devices that are connected not through a plug, but directly to the wires through the terminal block.